beautypg.com

System alarms, Other behaviors, Table 6.2—other symptoms 143 – Watlow CPC400 User Manual

Page 157

background image

CPC400 Series User’s Guide

Chapter 6: Troubleshooting and Reconfiguring

Doc. 0600-2900-2000

Watlow Anafaze

143

System Alarms

If the controller detects a hardware problem, it displays an
alarm message. The message persists until the condition is
corrected.

The CPC400 displays the following system alarm messages:

Low power: See Low Power on page 145.

Battery dead: See Battery Dead on page 145.

H/W failure: Ambient: See H/W Failure: Ambient on
page 146
.

H/W failure: Gain: See H/W Failure: Gain or Offset
on page 146
.

H/W failure: Offset: See H/W Failure: Gain or Offset
on page 146
.

Other Behaviors

Table 6.2 indicates potential problems with the system or
controller and recommends corrective actions.

Table 6.2

Other Symptoms

Symptom

Possible Causes

Recommended Action

Indicated tempera-
ture not as expected

Controller not communicating

Sensor wiring incorrect

Noise

See

Checking Analog Inputs on page 148.

CPC400 display is
not lit

Power connection incorrect

Check wiring and service. See

Wiring the

Power Supply on page 24.

Failed flash memory chip

Replace the flash memory chip. See
Replacing the Flash Memory Chip on page
154.

CPC400 damaged or failed

Return the CPC400 for repair. See

Return-

ing a Unit on page 140.

CPC400 display is
lit, but keys do not
work

Keypad locked

See

Keys Do Not Work on page 147.

Unacknowledged alarm

An alarm condition exists and has not been
acknowledged. See

How to Acknowledge

an Alarm on page 52.

CPC400 damaged or failed

Return the CPC400 for repair. See

Return-