beautypg.com

High deviation function, High deviation output, Low deviation value – Watlow CPC400 User Manual

Page 137: Low deviation function, Low deviation output

background image

CPC400 Series User’s Guide

Chapter 5: Menu and Parameter Reference

Doc. 0600-2900-2000

Watlow Anafaze

123

High Deviation Function

Choose whether the alarm functions as an alarm or as a
boost output, or disable the alarm.

Values: See Table 5.16 on page 122.
Default: off
Modbus and LogicPro: See Alarm Acknowledge on page
132
and
Alarm Function on page 133.

High Deviation Output

Choose a digital output to activate when the high deviation
alarm occurs. You cannot choose an output that is in use for
closed-loop control or for the Serial DAC clock.

Values: none (0) or output 1 to 34 (1 to 34). Values in pa-
rentheses are for serial communications and LogicPro.
Default: none (0)
Modbus Address (Loops 1 to 9): 40460 to 40468
Parameter Number: 27
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 27.1 to 27.9

Low Deviation Value

Enter the amount by which the process variable must fall
below the set point for the low deviation alarm to occur. For
more information, see Process Alarms on page 65.

Values: See Table 5.13 on page 113 for values and decimal
placement.
Default: Table 5.13 on page 113
Modbus Address (Loops 1 to 9): 40358 to 40366
Parameter Number: 21
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 21.1 to 21.9

Low Deviation Function

Choose whether the alarm functions as an alarm or as a
boost output, or disable the alarm.

Values: See Table 5.16 on page 122.
Default: off
Modbus and LogicPro: See Alarm Acknowledge on page
132
and
Alarm Function on page 133.

Low Deviation Output

Choose a digital output to activate when the low deviation
alarm occurs. You cannot choose an output that is in use for
closed-loop control or for the Serial DAC clock.

Values: none (0) or output 1 to 34 (1 to 34). Values in pa-
rentheses are for serial communications and LogicPro.

l01 HiDeviationr
func boff

l01 HiDeviationr
outputbnone

l01 LoDeviationr
value b 5 ˚F

l01 LoDeviationr
func boff

l01 LoDeviationr
outputbnone