Alarm functions, set points, hysteresis and delay set-
tings.
•
Soft integers 81 to 100 and soft Booleans 237 to 256.
If you have enabled remote job selection (see BCD Job Load
on page 97), you will see the message below, and you will
not be able to use the controller keypad to save a job.
Values: 1 to 8 (1 to 8) or none (0). Values in parentheses are
for serial communications and LogicPro.
Default: none (0)
Modbus Address: 44835
Parameter Number: 110
LogicPro Driver: Database
LogicPro Address: 110.1
BCD Job Load
Choose the digital input(s) to use for remote job selection.
The controller uses the states of the selected inputs as a bi-
nary code that specifies which job number to run (see
Table 5.3).
To save jobs into memory, use the Save setup as job param-
eter.
Values: See Table 5.3
Default: disabled (0)
Modbus Address: 44837
Parameter Number: 112
LogicPro Driver: Database
LogicPro Address: 112.1
Table 5.3
Values for BCD Job Load
Display
Value
Modbus or
LogicPro
Value
Description
use D/I 1
1
Use digital input 1 for remote selection of jobs 1 and 2.
use D/I 1-2
2
Use digital inputs 1 and 2 for remote selection of jobs 1 to 4.
use D/I 1-3
3
Use digital inputs 1 to 3 for remote selection of jobs 1 to 8.
disabled
0
Disable remote job selection
lSave setup as r
not available
lBCD job load r
bdisabled