Keypad Test

To test the keypad, press <. This screen will appear:

To test a key, press it. If the key is working properly, an
icon for that key appears.

When you are done testing the keypad, press >> to return
to the Keypad test parameter.

Test Digital Output 1 to 35

Use the Test D/O parameter to manually toggle a digital
output on and off. Choose on to sink the current from the
output to the controller common. Choose off to stop the cur-
rent flow. For instructions, see Digital Output Test on page
26
. You cannot toggle an output that is enabled for control.

NOTE!

When you exit the I/O tests menu, all outputs that
were forced on are turned off.

Values: off (0) or on (1)
Default: off (0)
Modbus Address (Digital Outputs 1 to 35): 40751 to
40785
Parameter Number: 47
LogicPro Driver: CPC400_Digital_Out
LogicPro Address (Digital Outputs 1 to 35): 1 to 35

Additional Parameters for Serial Communications
and LogicPro Programs

These parameters are available only for serial communica-
tions and LogicPro programs. They are not accessible
through the controller keypad.

Alarm Acknowledge

Indicates whether an alarm has been acknowledged. To ac-
knowledge an alarm, clear the bit for that alarm.
Table 5.19 shows which bit corresponds to each alarm. See
Bit-Wise Values on page 78 for information on reading or
setting this parameter.

This parameter is available only for serial communications
and LogicPro programs.