Mode Override
Choose the digital input to use for the mode override fea-
ture. When the input is activated, the controller sets all
loops to manual mode at the output levels specified at the
Sensor fail heat output and Sensor fail cool output parame-
ters in the Output menu.
Use the Mode override D/I active parameter to choose
which signal state activates the mode override feature.
Values: enabled by D/I1 to enabled by D/I8 (1 to 8) or dis-
abled (0). Values in parentheses are for serial communica-
tions and LogicPro.
Default: disabled (0)
Modbus Address: 44839
Parameter Number: 114
LogicPro Driver: Database
LogicPro Address: 114.1
WARNING!
Do not rely solely on the mode override feature to
shut down your process. Install external safety
devices or overtemperature devices for emergen-
cy shutdowns.
Mode Override Digital Input Active
Choose whether the on state (connected to controller com-
mon) or off state (open circuit) activates the mode override
feature.
Use the Mode override parameter to enable the mode over-
ride feature and select the digital input.
Values: on (0) or off (1). Values in parentheses are for seri-
al communications and LogicPro.
Default: on (0)
Modbus Address: 44840
Parameter Number: 115
LogicPro Driver: Database
LogicPro Address: 115.1
Logic Program
This parameter indicates whether a logic program is run-
ning. You can also use this parameter to run or stop a logic
program.
Values: running (1) or stopped (0). Values in parentheses
are for serial communications and LogicPro.
Default: stopped (0)
Modbus Address: 49481
Parameter Number: 150
LogicPro Driver: Database
LogicPro Address: 150.1