Zero calibration, Table 5.20—system status bits 137 – Watlow CPC400 User Manual
Page 151

CPC400 Series User’s Guide
Chapter 5: Menu and Parameter Reference
Doc. 0600-2900-2000
Watlow Anafaze
137
Values: See Table 5.20.
Modbus Address: 40786 (first to eighth bit), 40787 (ninth
to sixteenth bit)
Parameter Number: 48
LogicPro Driver: Database
LogicPro Address: 48.1 (first to eighth bit), 48.2 (ninth to
sixteenth bit)
Table 5.20
System Status Bits
Zero Calibration
This read-only parameter indicates the signal level detect-
ed when the controller measures its zero reference voltage
in performing its self-calibration. If the value drifts out of
specified limits, the controller places all loops in manual
mode at 0 percent power and indicates a hardware failure.
This parameter is available only for serial communications
and LogicPro.
Values: 0 to 32767 counts
Modbus Address: 40717
Parameter Number: 44
LogicPro Driver: Database
LogicPro Address: 44.1
Parameter
Description
Values
Bit
Battery Status
Indicates whether the values in RAM
have been corrupted while the power
has been off.
0: No corruption detected
1: Data corrupted
First
Ambient Status
Indicates whether the ambient tem-
perature is within the controller’s oper-
ating range. If the ambient is out of
range, the controller sets all loops to
manual mode at 0 percent power.
0: Within range
1: Outside of range
Fourth
Zero Status
Indicates whether the zero self-cali-
bration measurement falls within
acceptable limits.
0: In calibration
1: Out of calibration
Sixth
Full Scale Status
Indicates whether the full scale self-
calibration measurement falls within
acceptable limits.
0: In calibration
1: Out of calibration
Seventh
Power Up Alarm
Delay Status
Indicates whether the power-up alarm
delay feature is presently active. See
Power Up Alarm Delay on page 100.
0: Delay feature not active
1: Delay feature active
Ninth