CPC400 Series User’s Guide

Chapter 5: Menu and Parameter Reference

Doc. 0600-2900-2000

Watlow Anafaze

137

Values: See Table 5.20.
Modbus Address: 40786 (first to eighth bit), 40787 (ninth
to sixteenth bit)
Parameter Number: 48
LogicPro Driver: Database
LogicPro Address: 48.1 (first to eighth bit), 48.2 (ninth to
sixteenth bit)

Table 5.20

System Status Bits

Zero Calibration

This read-only parameter indicates the signal level detect-
ed when the controller measures its zero reference voltage
in performing its self-calibration. If the value drifts out of
specified limits, the controller places all loops in manual
mode at 0 percent power and indicates a hardware failure.
This parameter is available only for serial communications
and LogicPro.

Values: 0 to 32767 counts
Modbus Address: 40717
Parameter Number: 44
LogicPro Driver: Database
LogicPro Address: 44.1

Parameter

Description

Values

Bit

Battery Status

Indicates whether the values in RAM
have been corrupted while the power
has been off.

0: No corruption detected
1: Data corrupted

First

Ambient Status

Indicates whether the ambient tem-
perature is within the controller’s oper-
ating range. If the ambient is out of
range, the controller sets all loops to
manual mode at 0 percent power.

0: Within range
1: Outside of range

Fourth

Zero Status

Indicates whether the zero self-cali-
bration measurement falls within
acceptable limits.

0: In calibration
1: Out of calibration

Sixth

Full Scale Status

Indicates whether the full scale self-
calibration measurement falls within
acceptable limits.

0: In calibration
1: Out of calibration

Seventh

Power Up Alarm
Delay Status

Indicates whether the power-up alarm
delay feature is presently active. See
Power Up Alarm Delay on page 100.

0: Delay feature not active
1: Delay feature active

Ninth