Chapter 5: Menu and Parameter Reference
CPC400 Series User’s Guide
136
Watlow Anafaze
Doc. 0600-2900-2000
Major Part
Indicates the firmware version number to the left of the
decimal point, such as “1” for version 1.07A.
Modbus Address: 40844
Parameter Number: 52
LogicPro Driver: Database
LogicPro Address: 52.2
Minor Part
Indicates the firmware version number in the hundredths
place to the right of the decimal point, such as “7” for ver-
sion 1.07A.
Modbus Address: 40845
Parameter Number: 52
LogicPro Driver: Database
LogicPro Address: 52.3
Revision Letter
Indicates the ASCII code value for the firmware version let-
ter, if present, such as “65” (the ASCII value for “A”) for ver-
sion 1.07A.
Modbus Address: 40846
Parameter Number: 52
LogicPro Driver: Database
LogicPro Address: 52.4
Full Scale Calibration
This read-only parameter indicates the signal level detect-
ed when the controller measures its full scale reference
voltage in performing its self-calibration. If the value drifts
out of specified limits, the controller places all loops in
manual mode at 0 percent power and indicates a hardware
failure.
This parameter is available only for serial communications
and LogicPro programs.
Values: 0 to 32767 counts
Modbus Address: 40718
Parameter Number: 45
LogicPro Driver: Database
LogicPro Address: 45.1
System Status
Check the status of the specific system conditions listed in
Table 5.20. This parameter is available only for serial com-
munications and LogicPro programs. See Bit-Wise Values
on page 78 for information on reading this parameter.