Chapter 5: Menu and Parameter Reference

CPC400 Series User’s Guide

136

Watlow Anafaze

Doc. 0600-2900-2000

Major Part

Indicates the firmware version number to the left of the
decimal point, such as “1” for version 1.07A.

Modbus Address: 40844
Parameter Number: 52
LogicPro Driver: Database
LogicPro Address: 52.2

Minor Part

Indicates the firmware version number in the hundredths
place to the right of the decimal point, such as “7” for ver-
sion 1.07A.

Modbus Address: 40845
Parameter Number: 52
LogicPro Driver: Database
LogicPro Address: 52.3

Revision Letter

Indicates the ASCII code value for the firmware version let-
ter, if present, such as “65” (the ASCII value for “A”) for ver-
sion 1.07A.

Modbus Address: 40846
Parameter Number: 52
LogicPro Driver: Database
LogicPro Address: 52.4

Full Scale Calibration

This read-only parameter indicates the signal level detect-
ed when the controller measures its full scale reference
voltage in performing its self-calibration. If the value drifts
out of specified limits, the controller places all loops in
manual mode at 0 percent power and indicates a hardware
failure.

This parameter is available only for serial communications
and LogicPro programs.

Values: 0 to 32767 counts
Modbus Address: 40718
Parameter Number: 45
LogicPro Driver: Database
LogicPro Address: 45.1

System Status

Check the status of the specific system conditions listed in
Table 5.20. This parameter is available only for serial com-
munications and LogicPro programs. See Bit-Wise Values
on page 78
for information on reading this parameter.