Alarm status, Ambient sensor reading, Analog input – Watlow CPC400 User Manual

Page 148

background image

Chapter 5: Menu and Parameter Reference

CPC400 Series User’s Guide

134

Watlow Anafaze

Doc. 0600-2900-2000

Alarm Status

Indicates whether an alarm is active. Table 5.19 shows the
bit to set or read for each alarm. This parameter is avail-
able only for serial communications and LogicPro pro-
grams. See Bit-Wise Values on page 78 for information on
reading or setting this parameter.

Values: Not active (0) or active (1)
Modbus Address (Loops 1 to 9): 40392 to 40400
Parameter Number: 23
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 23.1 to 23.9

Table 5.19

Bit Positions for Alarm Status and
Alarm Acknowledge

Ambient Sensor Reading

This read-only parameter indicates the temperature mea-
sured by the cold-junction compensation sensor located
near the analog input terminal block.

This parameter is available only for serial communications
and LogicPro programs.

Values: Temperature in tenths of a degree Fahrenheit. To
convert to Celsius, use the formula °C = 5/9(°F - 32).
Modbus Address: 40579
Parameter Number: 34
LogicPro Driver: Database
LogicPro Address: 34.1

Analog Input

Indicates the value measured by the sensor after filtering
and scaling. This parameter is read-only.

Alarm

Bit

Low Deviation Alarm

Third

High Deviation Alarm

Fourth

Alarm Low

Fifth

Alarm High

Sixth

Thermocouple Reversed

Seventh

Thermocouple Shorted

Eighth

Thermocouple Open

Ninth

RTD Open

Tenth

RTD Shorted