beautypg.com

Global setup menu, Load setup from job, Save setup as job – Watlow CPC400 User Manual

Page 110

background image

Chapter 5: Menu and Parameter Reference

CPC400 Series User’s Guide

96

Watlow Anafaze

Doc. 0600-2900-2000

Global Setup Menu

Use the Global setup menu to set parameters that affect all
loops.

Load Setup From Job

Load one of the jobs stored in battery-backed RAM. The fol-
lowing parameters are loaded for each loop as part of a job:

PID constants, filter settings, set points and hystere-
sis.

Control mode (automatic or manual) and output power
levels (if the loop is in manual control)

Alarm functions, set points, hysteresis and delay set-
tings.

Soft integers 81 to 100 and soft Booleans 237 to 256.

If you have enabled remote job selection (see BCD Job Load
on page 97
), you will see the message below, and you will
not be able to use the controller keypad to load a job.

NOTE!

Current settings are overwritten when you select
a job from memory. Save your current settings to
another job number if you want to keep them.

Values: 1 to 8 (1 to 8) or none (0). Values in parentheses are
for serial communications and LogicPro.
Default: none (0)
Modbus Address: 44836
Parameter Number: 111
LogicPro Driver: Database
LogicPro Address: 111.1

Save Setup as Job

Save the current settings as one of eight jobs in the battery-
backed RAM. The following parameters are saved for each
loop as part of a job:

PID constants, filter settings, set points and hysteresis.

Control mode (automatic or manual) and output power
levels (if the loop is in manual control)

lGlobal setup r
Other menus b

lLoad setup r
from job bnone

lLoad setup r
not available

lSave setup as r
job bnone