Input menu, Input type, Input menu 104 – Watlow CPC400 User Manual
Page 118: Table 5.7—input types and ranges 104
Chapter 5: Menu and Parameter Reference
CPC400 Series User’s Guide
104
Watlow Anafaze
Doc. 0600-2900-2000
Input Menu
Use the Input menu to configure the process input:
•
Input type
•
Engineering units
•
Scaling, calibration and filtering.
Input Type
Choose the type of sensor that is connected to the analog in-
put.
Values: See Table 5.7. For the pulse loop (CPC404 loop 5
or CPC408 loop 9), the only choices are pulse (7) and skip
(10).
Default: J T/C (1); for the pulse loop, pulse (7)
Modbus Address (Loops 1 to 9): 40103 to 40111
Parameter Number: 6
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 6.1 to 6.9
Table 5.7
Input Types and Ranges
Display
Value
Modbus
or Logic
Value
Description
Input Range
J T/C
1
Type J thermocouple
-350 to 1400°F (-212 to 760°C)
K T/C
2
Type K thermocouple
-450 to 2500°F (-268 to 1371°C)
T T/C
3
Type T thermocouple
-450 to 750°F (-268 to 399°C)
S T/C
4
Type S thermocouple
0 to 3200°F (-18 to 1760°C)
R T/C
5
Type R thermocouple
0 to 3210°F (-18 to 1766°C)
B T/C
6
Type B thermocouple
150 to 3200°F (66 to 1760°C)
E T/C
20
Type E thermocouple
-328 to 1448°F (-200 to 787°C)
RTD
8
RTD
-328.0 to 1150.0°F (-200.0 to 621.1°C)
process
0
Voltage or current signal,
depending upon the hard-
ware configuration. See
Figure 1.2 on page 6.
Variable Retransmit on page 67.
pulse
7
Pulse input. Available only
for loop 5 on the CPC404
or loop 9 on the CPC408.
0 to 2000 Hz, scalable
skip
10
Loop is not used for con-
trol, does not report
alarms, and is not shown
on the scanning display.
(none)
l01 Input r
Other menus b
l01 Input type r
bJ T/C