Chapter 5: Menu and Parameter Reference
CPC400 Series User’s Guide
110
Watlow Anafaze
Doc. 0600-2900-2000
Table 5.10
Characters for the Loop Name and
Input Units Parameters
PV Source
Select whether an analog input or a soft integer is used for
the channel's feedback. When it is desirable to control
based on a value that is set by logic, for example an average
of two or more analog inputs, set the loop to take its feed-
back from a soft integer, and create a logic program to write
the desired value to the soft integer.
Table 5.11
PV Source Options
Values: input n (0) or soft integer n (1). Where n is the
channel number.
Default: input n (0)
Modbus Address: 45394 to 45411
Parameter: 136
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 136.1 to 136.9
Character
Display Values
ASCII Values
A to Z
A to Z
65 to 90
0 to 9
0 to 9
48 to 57
Degree symbol
˚
223
Percent sign
%
37
Forward slash
/
47
Space
.
32
Pound sign
#
35
Display Value
Modbus or
LogicPro Value
Description
input n
0
PV Source is the
analog input corre-
sponding to the loop
number.
soft
integer n
1
PV Source is the
soft integer corre-
sponding to the loop
number.
l01 PV source r
u input