Chapter 5: Menu and Parameter Reference

CPC400 Series User’s Guide

110

Watlow Anafaze

Doc. 0600-2900-2000

Table 5.10

Characters for the Loop Name and
Input Units Parameters

PV Source

Select whether an analog input or a soft integer is used for
the channel's feedback. When it is desirable to control
based on a value that is set by logic, for example an average
of two or more analog inputs, set the loop to take its feed-
back from a soft integer, and create a logic program to write
the desired value to the soft integer.

Table 5.11

PV Source Options

Values: input n (0) or soft integer n (1). Where n is the
channel number.
Default: input n (0)
Modbus Address: 45394 to 45411
Parameter: 136
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 136.1 to 136.9

Character

Display Values

ASCII Values

A to Z

A to Z

65 to 90

0 to 9

0 to 9

48 to 57

Degree symbol

˚

223

Percent sign

%

37

Forward slash

/

47

Space

.

32

Pound sign

#

35

Display Value

Modbus or

LogicPro Value

Description

input n

0

PV Source is the
analog input corre-
sponding to the loop
number.

soft

integer n

1

PV Source is the
soft integer corre-
sponding to the loop
number.