Chapter 2: Installation
CPC400 Series User’s Guide
42
Watlow Anafaze
Doc. 0600-2900-2000
Table 2.7
EIA/TIA-232 Connections
Jumpers in EIA/TIA-232 Connectors
Some software programs and some operator interface ter-
minals require a clear to send (CTS) signal in response to
their request to send (RTS) signal, or a data set ready
(DSR) in response to their data terminal ready (DTR). The
CPC400 is not configured to receive or transmit these sig-
nals. To use such software with the CPC400, jumper the
RTS to the CTS and the DTR to the DSR in the DB connec-
tor. Table 2.8 lists the standard pin assignments for DB-9
and DB-25 connectors.
Table 2.8
RTS/CTS and DSR/DTR Pins in
DB-9 and DB-25 Connectors
Cables manufactured by Watlow Anafaze for EIA/TIA-232
communications include these jumpers. Neither WAT-
VIEW nor LogicPro software requires these jumpers.
Figure 2.30 Connecting One CPC400 to a Com-
puter Using EIA/TIA-232
Wire
Color
CPC400
TB1
DB 9
Connector
DB 25
Connector
White
TX Pin 26
RX Pin 2
RX Pin 3
Red
RX Pin 25
TX Pin 3
TX Pin 2
Black
GND Pin 23
GND Pin 5
GND Pin 7
Green
GND Pin 24
N/U Pin 9
N/U Pin 22
Shield
N/C
GND Pin 5
GND Pin 7
DB-9
DB-25
RTS
7
4
CTS
8
5
DTR
4
20
DSR
6
6
EIA/TIA-232
cable