Write examples – Watlow CPC400 User Manual
Page 208
Appendix A: Modbus Protocol
CPC400 Series User’s Guide
194
Watlow Anafaze
Doc. 0600-2900-2000
Write Examples
The data written is echoed back to the controller. The fol-
lowing examples show sample query and response packets.
Example 1
The host query (Table A.5 on page 194) uses the multiple-
point write function to write a value of 20 to the proportion-
al band for loop 1 in a controller with address 1. The slave
responds (Table A.6 on page 194).
Table A.5
Sample Packet for Host Query
Table A.6
Sample Packet for Slave Response
Example 2
The host query (Table A.7 on page 194) uses the multiple-
point write function to write the values 30, 40, and 50 to the
proportional bands for loops 1 through 3 in a controller
with address 1. The slave responds (Table A.8 on page 194).
Table A.7
Sample Packet for Host Query
Table A.8
Sample Packet for Slave Response
Slave Address
Function
Start Address
Data
CRC
High
Low
High
Low
04
06
00
00
00
14
89
90
Slave Address
Function
Start Address
Data
CRC
High
Low
High
Low
04
06
00
00
00
14
89
90
Slave
Addr.
Func-
tion
Start
Address
No. of
Registers
Byte
Count
Data 1
Data 2
Data 3
CRC
Hi
Lo
Hi
Lo
Hi
Lo
Hi
Lo
Hi
Lo
01
10
00
00
00
03
06
00
1E
00
28
00
32
4F 5F
Slave Address
Function
Start Address
Number of Registers
CRC
High
Low
High
Low
01
10
00
00
00
03
80 08