Chapter 7: Specifications

CPC400 Series User’s Guide

174

Watlow Anafaze

Doc. 0600-2900-2000

Table 7.16

Input Resistance for Voltage Inputs

Table 7.17

Digital Inputs

Outputs

The controller directly accommodates switched dc and
open-collector outputs only. These outputs can be used to
control a wide variety of loads. They are typically used to
control solid-state relays or other power switching devices
which, in turn, devices such as heaters. They may also be
used to signal another device of an alarm condition in the
controller.

Analog outputs may be accomplished by using Dual DAC or
Serial DAC modules in conjunction with one of the control
outputs.

An open-collector CPU watchdog output is also provided so
that an external device can monitor the CPU state.

Analog Outputs

No direct analog outputs are provided.

Range

Input Resistance

0 to 12V

85 k

0 to 10V

50 k

0 to 5V

40 k

0 to 1V

7.4 k

0 to 500 mV

6.2 k

0 to 100 mV

1.2 k

Number

8

Configuration

8 selectable for output override, remote job
selection or programmable logic

Input Voltage Protection

Diodes to supply and common. Source must
limit current to 10 mA for overvoltage conditions

Voltage Levels

<1.3V = Low
>3.7V = High (TTL)
5V maximum, 0 V minimum

Maximum Switch Resistance to Pull Input Low

1 k

Minimum Switch Off Resistance

11 k

Response Time

50 ms (AC line frequency set to 60 Hz)
60 ms (AC line frequency set to 50 Hz)