Ratio set point differential, Soft integers menu, Soft integer value – Watlow CPC400 User Manual
Page 144: Soft integers menu 130
Chapter 5: Menu and Parameter Reference
CPC400 Series User’s Guide
130
Watlow Anafaze
Doc. 0600-2900-2000
Ratio Set Point Differential
Enter the value to add to the ratio calculation before using
it as the set point.
Values: -9999 to 9999. Decimal placement depends upon
the Input type and Disp format values in the Input menu.
Default: 0
Modbus Address (Loops 1 to 9): 44818 to 44826
Parameter Number: 109
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 109.1 to 109.9
Decimal Placement for Modbus or LogicPro: See Dec-
imal Placement for Numeric Values on page 80.
Soft Integers Menu
The Soft integers menu contains 1,100 user-definable, 16-
bit word registers. Use these parameters to read and set in-
teger data.
Read and write access are available through a logic pro-
gram, WatView HMI software, the controller display or a
third-party host.
Soft Integer Value
Read or set an integer value. For example, suppose that
you use serial communications to retrieve the input tem-
perature from four different inputs, and you have a pro-
gram that calculates the average input temperature. You
could write the average input temperature to one of the
Soft int parameters so that the operator could read it.
Values: -32768 to 32767
Default: 0
Modbus Address (Soft Integers 1 to 100): 44883 to
44982
Modbus Address (Soft Integers 101 to 1100): 45496 to
46496
Parameter Number (Soft Integers 1 to 100): 126
Parameter Number (Soft Integers 101 to 1100): 140
LogicPro Driver: Soft_Int
LogicPro Address: 1 to 1100
NOTE!
The values of soft integers 81 to 100 are saved in
jobs, and the values of soft integers 1 to 80 and
101 to 1100 are not.
l01 Ratio SP r
diff b 0 ˚F
lSoft integers r
Other menus b
lSoft int 1 r
value= b 0