Soft Booleans Menu
The Soft Booleans menu contains 256 one-bit Boolean reg-
isters. Use these parameters to read and set Boolean (true
or false) data.
Read and write access are available through a logic pro-
gram, WatView, the controller display or a third-party
host.
Soft Boolean Value
Read or set a true or false value.
Values: 0 (false) or 1 (true)
Default: 0
Modbus Address (Soft Boolean 1 to 256): 44983 to
45238
Parameter Number: 127
LogicPro Driver: Soft_Bool
LogicPro Address (Soft Boolean 1 to 256): 1 to 256
NOTE!
The values of soft Booleans 237 to 256 are saved
in jobs, the values of soft Booleans 1 to 236 are
not.
I/O Tests Menu
Use the I/O tests menu to test the following:
•
Digital inputs
•
Digital outputs
•
Keypad
Digital Inputs
This parameter indicates the states of the eight digital in-
puts. A 1 indicates that the input is connected to controller
common (on). A 0 indicates an open circuit (off).
To test an input, short it to controller common. When the
input is shorted, its input state should be 1. For detailed in-
structions, see Digital Input Test on page 27.
The controller display shows the states of digital inputs 1
to 8 from left to right. For serial communications and Log-
icPro programs, read the state of one input at a time.
Values: 0 if the input is off, 1 if the input is on
Modbus Address (Digital Inputs 1 to 8): 40719 to 40726
Parameter Number: 46
LogicPro Driver: CPC400_Digital_In
LogicPro Address (Digital Inputs 1 to 8): 1 to 8
lSoft Booleans r
Other menus b
lSoft Bool 1r
value= b0
lI/O tests r
Other menus b
lDigital inputsr
00000000 1=on