Table 7.15—rtd range and resolution 173 – Watlow CPC400 User Manual
Page 187
![background image](/manuals/359052/187/background.png)
CPC400 Series User’s Guide
Chapter 7: Specifications
Doc. 0600-2900-2000
Watlow Anafaze
173
Table 7.13
Programmable Logic
Table 7.14
Thermocouple Range and
Resolution
* True for 10 percent to 100 percent of span except type B, which is specified
for 800°F to 3200°F.
Table 7.15
RTD Range and Resolution
Programming Languages
Ladder diagram, sequential function chart, function block dia-
gram (IEC 1131-3)
Number of Instructions
7 logic instructions, 42 function block instructions
Memory
64K flash, nonvolatile
Program Execution
Logic program runs concurrently with closed-loop control
Read/Write Access
Controller I/O and closed-loop control parameters
Logic Programming Software
LogicPro
Programming Environment
Windows 95, Windows 98, Windows NT, Windows 2000
Thermocouple
Type
Range in ˚F
Range in ˚C
Accuracy* at
25°C Ambient
Accuracy* at
0 to 50°C Ambient
˚F
˚C
˚F
˚C
J
-350 to 1400
-212 to 760
±2.2
±1.2
±3.3
±1.8
K
-450 to 2500
-268 to 1371
±2.4
±1.3
±3.8
±2.1
T
-450 to 750
-268 to 399
±2.9
±1.6
±5.8
±3.2
S
0 to 3200
-18 to 1760
±5.0
±2.8
±8.8
±4.9
R
0 to 3210
-18 to 1766
±5.0
±2.8
±8.8
±4.9
B
150 to 3200
66 to 1760
±7.2
±4.0
±22.1
±12.3
E
-328 to 1448
-200 to 787
±1.8
±1.0
±2.9
±1.6
Range
in ˚F
Range
in ˚C
Resolution
in ˚C
Measurement
Temperature in
˚C
Accuracy at
25˚C Ambient
Accuracy at
0 to 50˚C Ambient
˚F
˚C
˚F
˚C
-328.0
to
1150.0
-200.0
to
621.1
0.07
25
0.9
0.5
1.2
0.5
400
2.7
1.5
4.1
2.2