EIA/TIA-485 Interface

To communicate with more than one CPC400 series con-
troller on a controller network, or to use communication ca-
ble lengths greater than 50 feet (15 m) from PC to
controller, you must use EIA/TIA-485 communications.

When using EIA/TIA-485 communications, you must at-
tach a 232-to-485 converter to the computer. Figure 2.31
and Figure 2.32 show the recommended system wiring.

Figure 2.31 Four-Wire EIA/TIA-485 Wiring

Figure 2.32 Two-Wire EIA/TIA-485 Wiring

Personal
Computer

232-to 485

Converter

First

CPC400

Last

CPC400

TXA/TDA/TX-

TXB/TDB/TX+

RXA/RDA/RX-

RXB/RDB/RX+

RXA 25

RXB 23

TXA 26

TXB 24

RXA 25

RXB 23

TXA 26

TXB 24

Do not

connect

shield to
CPC400.

JU1

A
B

JU1

A
B

Personal
Computer

232-to 485

Converter

First

CPC400

Last

CPC400

TXA/TDA/TX-

TXB/TDB/TX+

RXA/RDA/RX-

RXB/RDB/RX+

RXA 25

RXB 23

TXA 26

TXB 24

RXA 25

RXB 23

TXA 26

TXB 24

Do not

connect

shield to
CPC400.

JU1

A
B

JU1

A
B