CPC400 Series User’s Guide

Chapter 5: Menu and Parameter Reference

Doc. 0600-2900-2000

Watlow Anafaze

115

Figure 5.3

The Effect of Tune Gain on
Recovery from a Load Change

Overshoot Reduction

Enter the amount of overshoot reduction. A larger value
yields less overshoot.

Values: 0% (0) to 100% (100)
Default: 50% (50)
Modbus Address (Loops 1 to 9): 46576 to 46584
Parameter Number: 146
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 146.1 to 146.9

Control Type

Choose a control algorithm.

Table 5.14

Control Types

Values: PID1 (0) or PID2 (1)
Default: PID1 (0)
Modbus Address (Loops 1 to 9): 45480 to 45489
Parameter Number: 139
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 139.1 to 139.9

Control Type

Description

PID1

Heat and cool outputs used to control.
Only one output may be on at a time.

PID2

Heat and cool outputs used to control.
Both outputs can be on at the same time.

l01 Overshoot r
reduction b 50%

l01 Control r
type bPID1