beautypg.com

Mounting the dual dac or serial dac module, Figure 2.10—dual dac and serial dac dimensions 19, Jumpers – Watlow CPC400 User Manual

Page 33: Mounting, Figure 2.10 dual dac and serial dac dimen- sions

background image

CPC400 Series User’s Guide

Chapter 2: Installation

Doc. 0600-2900-2000

Watlow Anafaze

19

Mounting the Dual DAC or Serial DAC Module

This section describes how to mount the optional Dual DAC
and Serial DAC digital-to-analog converters.

Mounting of the Dual DAC and Serial DAC is essentially
the same, except that the dimensions differ.

Jumpers

The output signal range of the Dual DAC and Serial DAC
modules is configured with jumpers. See Configuring Dual
DAC Outputs on page 163
and Configuring Serial DAC
Outputs on page 162
for information about setting these
jumpers.

Mounting

1.

Choose a location. The unit is designed for wall mount-
ing. Install it as close to the controller as possible.

2.

Mark and drill four holes for screw mounting. Holes
accommodate #8 (3.5 mm) screws. See Figure 2.10 for
screw locations. Install the unit with the four screws.

Figure 2.10 Dual DAC and Serial DAC Dimen-

sions

3.00 in

3.7 in

Electrical
Connectors

Electrical
Connectors

Dual DAC

3.00 in

3.62 in

4.7 in

Electrical

Connectors

Serial DAC

4.40 in

5.40 in

0.3 in

(8 mm)

(76 mm)

(91 mm)

(119 mm)

(137 mm)

(76 mm)

3.62 in

(91 mm)

(94 mm)

1.75 in

(44 mm)

(112 mm)

0.37 in

(9 mm)

0.65 in

(17 mm)

1.75 in

(44 mm)

0.65 in

(17 mm)

0.37 in
(9 mm)

0.3 in

(8 mm)

Electrical
Connectors

4 Holes for #8 (3.5 mm)

Screws or Bolts

4 Holes for #8 (3.5 mm)

Screws or Bolts