beautypg.com

Structural specifications – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 78

background image

Chapter 4 Specifications

4-13

„Structural Specifications

Inst

allation

Grounding

Grounding resistance of 100

Ω 2mm

2

or thicker wire, or your country’s

applicable standard.
(Same for FG and SG terminals)

Structure

*1

*1

The front face of the GP unit, installed in a solid panel, has been tested using conditions
equivalent to the standards shown in the specification. Even though the GP unit’s level of
resistance is equivalent to these standards, oils that should have no effect on the GP can
possibly harm the unit. This can occur in areas where either vaporized oils are present, or
where low viscosity cutting oils are allowed to adhere to the unit for long periods of time. If
the GP’s front face protection sheet becomes peeled off, these conditions can lead to the
ingress of oil into the GP and separate protection measures are suggested.
Also, if non-approved oils are present, it may cause deformation or corrosion of the front
panel’s plastic cover. Therefore, prior to installing the GP be sure to confirm the type of
conditions that will be present in the GP’s operating environment.
If the installation gasket is used for a long period of time, or if the unit and its gasket are
removed from the panel, the original level of the protection cannot be guaranteed. To
maintain the original protection level, be sure to replace the installation gasket regularly.

• GP-3300 Series, except AGP-3300U

Rating: Equivalent to IP65f NEMA #250 TYPE 4X/13
(Front surface at panel embedding)
Feature size: All-in-one
Installation configuration: Panel embedding

• AGP-3300U

Rating: IP65f NEMA #250 TYPE 1
(Front surface at panel embedding)
Feature size: All-in-one
Installation configuration: Panel embedding

Cooling Method

Natural air circulation

Weight Approx.

1.0kg[2.2lb] max. (unit only)
1.2kg[2.6lb] max (DIO/FLEX NETWORK/CANopen board type)

External
Dimensions

W167.5mm[6.59in] X H135mm[5.31in] X D59.5mm[2.34in]

Panel Cut
Dimensions

W156.0mm[6.14in] X H123.5mm[4.86in]

*2

Panel Thickness: 1.6mm[0.06in] to 5.0mm[0.20in]

*3

*2

As for dimensional tolerance everything +1/-0mm[+0.04/-0in] and R in angle are below
R3[R0.12in].

*3

Even if panel thickness is within recommend range for “Panel Cut Dimensions”, the panel
could warp, depending on panel’s material, size, and installation location of GP or other
devices. To prevent panel warpage, the installation surface may need to be strengthened.