When the ac type – Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 179

GP3000 Series Hardware Manual
8-8
When the AC type
Power Cord Specifications
Connecting the Power Cord
When connecting the AC type power cord, be sure to follow the procedures given below.
(1)
Be sure that the GP’s power cord is not plugged in to the power supply.
(2)
Remove the Terminal Srtip’s clear plastic cover.
(3)
Remove the screws from the two (2) terminals (L, N) and FG (Frame Ground) Terminal, position the
Ring Terminals and reattach the screws. (Check each wire to make sure the connections are correct.)
(4)
Reattach the Terminal Strip’s clear plastic cover.
• Use copper conductors only.
AC Power Cord
Grounding Wire
Power Cord
Double-insulated Wire
1.25 to 2.0mm
2
(16-14AWG)
1.25 to 2.0mm
2
(16-14AWG)
Recommended
Ring Terminal
*1
*1
In order to prevent a short circuit caused by loose screws, make sure to
use a crimp-type terminal with insulating sleeve.
J.S.T. Mfg. Co., Ltd
V2-MS3 compatible
J.S.T. Mfg. Co., Ltd
V2-P4 compatible
• The torque required to tighten these screws are as follows:
Terminal Block: 0.5 to 0.6N
•m[5-7Lb•In.]
FG (Frame Ground) Terminal: 0.6 to 0.7N
•m
l
ess than
6.0mm
Φ3.2mm or more
l
ess than
7.0mm
Φ4.3mm or more
FG (Frame Ground) Terminal
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"