beautypg.com

1 gp-3200 series, 1 general specifications, Gp-3200 series – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 67

background image

GP3000 Series Hardware Manual

4-2

4.1

GP-3200 Series

4.1.1

General Specifications

„Electrical Specifications

„Environmental Specifications

Power Supply

Input Voltage

DC24V

Rated Voltage

DC19.2 to 28.8V

Allowable Voltage Drop

2ms (max.)

Power Consumption

13W (max.)

In-Rush Current

60A (max.)

*1

*1

Half width (Time duration with a current exceeding 30A): 40

µs max.

Voltage Endurance

AC1000V 20mA for 1 minute
(between charging and FG terminals)

Insulation Resistance

DC500V 10M

Ω (min.)

(between charging and FG terminals)

Physical

Surrounding Air
Temperature

0 to 50°C

*1

*1

In the case of AGP-3200A, Extended use in environments where Surrounding air temperature is 40°C or
higher may degrade the display quality and result in decreased contrast.

Storage Temperature

-20 to +60°C

Ambient Humidity

10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)

Storage Humidity

10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)

Dust

0.1mg/m

3

and below (non-conductive levels)

Pollution Degree

For use in Pollution Degree 2 environment

Atmosphere

Free of corrosive gases

Air Pressure Vibration
Resistance (altitude
range)

800 to 1114hPa
(2,000 meters above sea-level and below)

Mechanical

Vibration Resistance

IEC61131-2 compliant
5 to 9Hz single-amplitude 3.5mm
9 to 150Hz constant-accelerated velocity 9.8m/s

2

X,Y,Z directions for 10 cycle (100 minute)

Concussion Resistance

IEC61131-2 compliant
(147m/s

2

X,Y,Z directions for 3 time)

Electrical

Noise Immunity

Noise Voltage: 1000V

P-P

Pulse Duration: 1

µs

Rise Time: 1ns
(via noise simulator)

Electrostatic Discharge
Immunity

6kV (complies with EN 61000-4-2 Level 3)