Chapter 6 FLEX NETWORK Connector

6-3

6.1.2

Flex Network Data Transfer Settings

6.2

Wiring to the FLEX NETWORK Connector

6.2.1

FLEX NETWORK Communication Cable

Use the following FLEX NETWORK Communication Cable when connecting to the FLEX NETWORK

Unit.

Communication Type

1:N

Connection Method

Multi Drop

Transfer Distance

At 6Mbps 200m per CH, at 12Mbps100m per CH

Transfer Method

During cyclic period, distributed transmission, Half-duplex

Transfer Speed

6Mbps, 12Mbps

Transfer I/F

Differential method, Pulse transfer resistance

Error Check

Format check, bit check, CRC-12 check

No. of Stations

63 stations max., Bit variable input: 512 points

*1

, Bit variable output:

512 points

*1

, Integer variable input: 128 points

*2

, Integer variable

output: 128 points

*2

(depending on type of units used.)

*1

When using GP-Pro EX under Ver.2.50, Bit variable enables to input/output 256 points.

*2

When using GP-Pro EX under Ver.2.50, Integer variable enables to input/output 64 points.

For details about the FLEX NETWORK, refer to the user manual for the respective FLEX NET-

WORK product.

Model

Length per Unit

FN-CABLE2010-31-MS

10m

FN-CABLE2050-31-MS

50m

FN-CABLE2200-31-MS

200m