5. Data Entry

77

(2) Work part was not contacted (missed)

The position complete signal will not turn ON if the actuator does not yet contact the work part after moving the

distance set in the “Positioning band” field.

Therefore, include a timeout check process in the sequence circuit on the PLC side.

(3) Work part moves during push & hold operation

[1] The work part moves in the pushed direction

If the work part moves in the pushed direction after the push & hold operation has completed, the actuator will

chase the work part within the positioning band.

If the current drops below the current-limiting value set in the “Push” field of the position table, the position

complete signal will turn OFF. The signal will turn ON when the current rises to or above the current-limiting value

again.

[2] The work part moves in the opposite direction

(The actuator is pushed back by a strong reactive force of the work part.)

If the actuator is pushed back after the push & hold operation has completed because the actuator thrust is

smaller than the reactive force of the work part, the actuator will be pushed back all the way until its thrust

balances out with the reactive force of the work part.

The position complete signal remains ON.

(Note) If the actuator is pushed back to the target position, an alarm will occur.

Speed

If the actuator does not contact

the load, the position complete

signal does not turn ON.

Moving distance

Positioning band

(Maximum push distance)

Target position

Speed

Moving distance

Positioning band

(Maximum push distance)

Target position

Position where the push

& hold operation is

determined complete

If the load moves forward, the

actuator chases the load within

the positioning band.

Speed

Moving distance

Positioning band

(Maximum push distance)

Target position

Position where the push

& hold operation is

determined complete