12 Functional Descriptions
04.96
12.20 Extended stop and retract (ESR) (SW 4 and higher)
–
Application of internal sources:
-
Emergency retraction threshold FA/FS,
-
611D DC link voltage threshold, drive MD 1634,
-
611D generator speed threshold, drive MD 1635
which must initiate a retraction operation.
–
Definition of internal reactions to be initiated in the case of a retraction operation:
-
Alarm and mode group stop
-
Retraction operation as open-loop control function and/or as
-
Autonomous drive function
•
Drive parameters for the "Extended stop and retract" function (611D)
–
DC link voltage threshold, drive MD 1631: If the voltage drops below this limit, a
drive defined as the generator axis switches to generator mode.
–
Voltage step, drive MD 1632: This value defines the upper threshold of the two-
position controller for generator operation.
–
DC link voltage threshold, drive MD 1633: If the voltage exceeds this limit value,
the drive switches from generator mode back to normal operation.
–
DC link voltage threshold, drive MD 1634: If the voltage drops below this limit,
emergency retraction measures can be initiated according to user specifications
(via MD or programming).
–
Generator speed threshold, drive MD 1635: If the speed drops below this value,
emergency retraction measures can be initiated according to user specifications
(via MD or programming).
2.) The possibility of controlling the function via the PLC:
•
Channel-specific
–
To PLC:
-
ESR monitoring is active
-
ESR reaction is initiated
•
Axis/spindle-specific
–
From PLC:
-
Activate ESR monitoring
-
Disable ESR monitoring
-
Enable ESR reaction
–
To PLC:
-
ESR monitoring is active
-
ESR reaction is initiated
-
ESR reaction is programmed
-
611D ZK2 messages
•
If monitoring is switched on from the PLC, it can be switched off from the PLC only.
•
If monitoring is switched off from the PLC, it is switched off for all channels.
12–214
© Siemens AG 1992 All Rights Reserved 6FC5197- AA50