7 Drive Machine Data (SIMODRIVE Drive MD)
09.95
7.3.2 Drive MD (data description)
Note:
Before the filter type is configured, the appropriate filter machine data must be input.
Time constant speed setpoint filter 1
1502
Default value
Lower input limit
Upper input limit
Units
0.0
0.0
500.0
ms
Active
at once
Input of time constant for speed setpoint filter 1 (PT1 low-pass). The filter is deactivated when
the data is set to zero.
Time constant speed setpoint filter 2
1503
Default value
Lower input limit
Upper input limit
Units
0.0
0.0
500.0
ms
Active
at once
Input of time constant for speed setpoint filter 2 (PT1 low-pass). The filter is deactivated when
the data is set to zero.
Natural frequency speed setpoint filter 1
1506
Default value
Lower input limit
Upper input limit
Units
2 000.0
10.0
8 000.0
Hz
Active
at once
Input of natural frequency for speed setpoint filter 1 (PT2 low-pass). An entry of < 10 Hz as
the natural frequency of the low-pass filter initializes the filter as a proportional element with a
gain of 1 independently of the associated damping. The filter is activated via machine data MD
1500 (No. speed setpoint filters) and MD 1501 (Type speed setpoint filter).
Note:
With interpolating axes, the speed setpoint filter must always be parameterized immediately.