7 Drive Machine Data (SIMODRIVE Drive MD)
07.97
7.3.2 Drive MD (data description)
P gain flux controller
1150
Default value
Lower input limit
Upper input limit
Units
400.0
0.0
100 000.0
A/Vs
Active
at once
Input of the proportional gain of the flux controller or automatic paramterization (initialization)
through the operator action Calculate controller data.
Note:
This data is relevant only for MSD drives.
Integral-action time flux controller
1151
Default value
Lower input limit
Upper input limit
Units
10.0
0.0
500.0
ms
Active
at once
Input of the control variable integral-action time flux controller or automatic paramterization by
the operator action Calculate controller data.
Speed for start of flux detection
1160
Default value
Lower input limit
Upper input limit
Units
1 500.0
200.0
50 000.0
rev/min
Active
at once
Above the set speed flux detection is active, below the set speed a flux model is used. The
parameter default is set for "Calculate controller data" and should not be changed.
Note:
This machine data only applies to main spindle drives.
DC link fixed voltage
1161
Default value
Lower input limit
Upper input limit
Units
600
0 (as from SW 6)
0
700
V
Active
at once
By specifying a DC link fixed voltage > 0V DSP internal DC link measurement is deactived
here, i.e. MD 1701 (between loop voltage display) is inactive (display: "
*
").
The given voltage is included instead of the measurement in:
•
DC link adaptation
•
Flux acquisition (MSD)
The permissibility of an activation of the DC link measurement (MD 1161=0) is monitored in
accordance with hardware configuration 5 (error message 300765).
Caution:
It is not possible to activate emergency retractive functions with deactivated DC link
measurement (MD 1161 > 0) (error message 300764).