7 Drive Machine Data (SIMODRIVE Drive MD)
7.3.2 Drive MD (data description)
Damping current setpoint filter 4
1209
Default value
Lower input limit
Upper input limit
Units
1.0
0.05
5.0
–
Active
at once
Input of damping for current setpoint filter 4 (PT2 low-pass). The filter is activated via machine
data MD 1200 (No. current setpoint filters) and MD 1201 (Type current setpoint filter).
Block frequency current setpoint filter 1
1210
Default value
Lower input limit
Upper input limit
Units
3 500.0
1.0
7 999.0
Hz
Active
at once
Input of block frequency for current setpoint filter 1 (band-stop). When block frequencies of <
10 Hz are input, the filter is deactivated (proportional element with a gain of 1). The filter is
activated via machine data MD 1200 (No. current setpoint filters) and MD 1201 (Type current
setpoint filter).
Note:
The maximum block frequency input value is limited by the sampling frequency of the servo
control (MD 1000) (parameterization error).
MD 1210
2 x T
sampl. I-controller
1
T
sampl.
(MD 1000)
62.5
µ
s
125.0
µ
s
MD 1210
8000 Hz
4000 Hz
= MD 1000 [ s ]
©
Siemens AG 1992 All Rights Reserved 6FC5197- AA50
7–105