7 Drive Machine Data (SIMODRIVE Drive MD)
08.96
7.3.2 Drive MD (data description)
Band-stop filter natural frequency set speed filter 2
1521
Default value
Lower input limit
Upper input limit
Units
100
1
141
%
Active
at once
The description of this machine data is the same as that for machine data MD 1520!
Concealable alarms (Power On)
1600
Default value
Lower input limit
Upper input limit
Units
0000
0000
FFFF
Hex
Active
at once
This machine data allows power on 611D alarms to be concealed. The monitoring function is
activated if the appropriate bit = 0. All 611D monitoring functions are activated as standard.
Value table:
Bit 0
Internal error cannot be concealed
Bit 1
Space vector monitoring (as from SW 5 FDD/MSD)
Bit 2
Not assigned
Bit 3
Not assigned
Bit 4
Measuring circuit, motor measuring system
Bit 5
Absolute track monitoring
Bit 6
Not assigned
Bit 7
Not assigned
Bit 8
Zero mark monitoring, motor measuring system
Bit 9
Converter limit frequency too high
Bit 10
Medium frequency measurement, speed too high - not concealable
Bit 11
Medium frequency measured-value memory full - not concealable
Bits 12-14
Not assigned
Bit 15
Power section temperature monitor
7–134
©
Siemens AG 1992 All Rights Reserved 6FC5197- AA50
SINUMERIK 840C (IA)