beautypg.com

Ge 86) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 96

background image

86

Explanation of functions (parameters)

2.3.18 Biases and gains of the frequency setting voltage (current)

(Pr. 38

, Pr. 39

, C2

to C7

)

*1.Factory settings may differ because of calibration parameters.
*2.The parameter number in parentheses is the one for use with the parameter unit (FR-PU04).

You can set the magnitude (slope) of the output frequency as desired in relation
to the external frequency setting signal (0 to 5V, 0 to 10V or 4 to 20mADC).
The "bias" and "gain" functions are used to adjust the relationship between the
input signal entered from outside the inverter to set the output frequency, e.g. 0
to 5V, 0 to 10V or 4 to 20mADC, and the output frequency.

Parameter

Name

Factory Setting

Setting

Range

Remarks

38

Frequency setting voltage gain
frequency

60Hz

1 to 120Hz

Setting is enabled
when Pr. 30 = "1".

39

Frequency setting current gain
frequency

60Hz

1 to 120Hz

C2 (902) *2

Frequency setting voltage bias
frequency

0Hz

0 to 60Hz

C3 (902) *2 Frequency setting voltage bias

0% *1

0 to 300%

C4 (903) *2 Frequency setting voltage gain

96% *1

0 to 300%

C5 (904) *2

Frequency setting current bias
frequency

0Hz

0 to 60Hz

C6 (904) *2 Frequency setting current bias

20% *1

0 to 300%

C7 (905) *2 Frequency setting current gain

100% *1

0 to 300%

POINT

Bias setting for 0-5VDC (0-10VDC) input

Use calibration parameters C2, C3

for setting.

Gain setting for 0-5VDC (0-10VDC) input

Use Pr. 38, calibration parameter

C4 for setting.

Bias setting for 4-20mADC input

Use calibration parameters C5, C6

for setting.

Gain setting for 4-20mADC input

Use Pr. 39, calibration parameter

C7 for setting.

(For 4 to 20mADC input, set "4" in any of Pr. 60 to Pr. 63 (input terminal
function selection) and assign AU (current input selection) to any of terminals
RH, RM, RL and STR, and turn on the AU signal.)

Frequency setting voltage signal

Factory setting

0Hz( )

C2

5V or 10V

(100% C4 *1)

0V

Pr.73

Output

frequency (Hz)

( Pr.38 )

Frequency setting current signal

20mA

4mA

Factory setting

( Pr.39 )

Output

frequency (Hz)

0Hz( )

C5

(0% C3 *1)

(Across
terminals
2-5)

(20% C6 *1)

(100% C7 *1)

(Across
terminals
4-5)

60Hz

60Hz

This manual is related to the following products: