MITSUBISHI ELECTRIC FR-S520E User Manual
Page 146
136
Communication parameters
2) Operation mode-based functions
*1. As set in the communication parameters n8 "operation command source" and n9 "speed
command source". (refer to page 152)
*2. At occurrence of RS-485 communication error, the inverter cannot be reset from the computer.
*3. As set in Pr. 75 "reset selection/PU stop selection".
*4. As set in Pr. 77 "parameter write disable selection".
Operation
Location
Item
Operation Mode
PU operation
External
operation
Computer link
operation
Operation panel
or FR-PU04
Run command
(start)
Enabled
Enabled
(Combined
operation mode)
Disabled
Running frequency
setting
Enabled
Enabled
(Combined
operation mode)
Disabled
Monitoring
Enabled
Enabled
Enabled
Parameter write
Enabled (*4)
Disabled
Disabled
Parameter read
Enabled
Enabled
Enabled
Inverter reset
Enabled
Enabled
Enabled
Stop command
Enabled
Enabled (*3)
Enabled (*3)
On-computer
user program by
RS-485
communication
Run command
Disabled
Disabled
Enabled (*1)
Running frequency
setting (*)
Disabled
Disabled
Enabled (*1)
Monitoring
Enabled
Enabled
Enabled
Parameter write
Disabled
Disabled
Enabled (*4)
Parameter read
Enabled
Enabled
Enabled
Inverter reset
Disabled
Disabled
Enabled (*2)
Stop command
Disabled
Disabled
Enabled
Control circuit
external terminal
Inverter reset
Enabled
Enabled
Enabled
Run command
Enabled
(Combined
operation mode)
Enabled
Enabled (*1)
Frequency setting
Enabled
(Combined
operation mode)
Enabled
Enabled (*1)
CAUTION
* When the user program of the computer is used to make the running frequency
setting by RS-485 communication, setting can be made in the minimum setting
increments of 0.01Hz, but the setting may be written to the inverter in increments
of 0.1Hz. (0 is written in the second decimal place.)
POINT
To perform parameter write, give an operation command, make inverter reset, etc. using
RS-485 communication, the operation mode must be changed to the "computer link
operation mode".
Set "0", "2", "7" or "8" in Pr. 79 "operation mode selection" to select the external operation
mode, and change the operation mode to the "computer link operation mode" in either of
the following methods.
1) Set "1" in the communication parameter n10 "link startup mode selection" to start the
inverter in the "computer link operation mode" at power on. (Refer to page 153 for the
communication parameter n10.)
2) Using operation mode write (instruction code HFB), write H0000 to choose the
"computer link operation mode". (Refer to page 146 for operation mode write.)