136

Communication parameters

2) Operation mode-based functions

*1. As set in the communication parameters n8 "operation command source" and n9 "speed

command source". (refer to page 152)

*2. At occurrence of RS-485 communication error, the inverter cannot be reset from the computer.
*3. As set in Pr. 75 "reset selection/PU stop selection".
*4. As set in Pr. 77 "parameter write disable selection".

Operation

Location

Item

Operation Mode

PU operation

External

operation

Computer link

operation

Operation panel
or FR-PU04

Run command
(start)

Enabled

Enabled

(Combined

operation mode)

Disabled

Running frequency
setting

Enabled

Enabled

(Combined

operation mode)

Disabled

Monitoring

Enabled

Enabled

Enabled

Parameter write

Enabled (*4)

Disabled

Disabled

Parameter read

Enabled

Enabled

Enabled

Inverter reset

Enabled

Enabled

Enabled

Stop command

Enabled

Enabled (*3)

Enabled (*3)

On-computer
user program by
RS-485
communication

Run command

Disabled

Disabled

Enabled (*1)

Running frequency
setting (*)

Disabled

Disabled

Enabled (*1)

Monitoring

Enabled

Enabled

Enabled

Parameter write

Disabled

Disabled

Enabled (*4)

Parameter read

Enabled

Enabled

Enabled

Inverter reset

Disabled

Disabled

Enabled (*2)

Stop command

Disabled

Disabled

Enabled

Control circuit
external terminal

Inverter reset

Enabled

Enabled

Enabled

Run command

Enabled

(Combined

operation mode)

Enabled

Enabled (*1)

Frequency setting

Enabled

(Combined

operation mode)

Enabled

Enabled (*1)

CAUTION

* When the user program of the computer is used to make the running frequency

setting by RS-485 communication, setting can be made in the minimum setting
increments of 0.01Hz, but the setting may be written to the inverter in increments
of 0.1Hz. (0 is written in the second decimal place.)

POINT

To perform parameter write, give an operation command, make inverter reset, etc. using
RS-485 communication, the operation mode must be changed to the "computer link
operation mode".
Set "0", "2", "7" or "8" in Pr. 79 "operation mode selection" to select the external operation
mode, and change the operation mode to the "computer link operation mode" in either of
the following methods.
1) Set "1" in the communication parameter n10 "link startup mode selection" to start the

inverter in the "computer link operation mode" at power on. (Refer to page 153 for the
communication parameter n10.)

2) Using operation mode write (instruction code HFB), write H0000 to choose the

"computer link operation mode". (Refer to page 146 for operation mode write.)