148

Communication parameters

5

Set frequency
read (RAM)

H6D

•When Pr. 37 = "0" (factory setting)

The set frequency (RAM or E

2

PROM) is read.

H0000 to H2EE0: 0.01Hz increments

•When Pr. 37 = "0.1 to 999", expansion link parameter

(HFF) = 0
The set speed is read.
H0000 to H03E7: 1r/min increments

4 digits

(6 digits)

Set frequency
read
(E

2

PROM)

H6E

•When Pr. 37 = "0.1 to 999", expansion link parameter

(HFF) = 1
The set speed is read. (The number of data digits is 6
digits.)
H0000 to HF3E58: 0.001r/min increments

Set frequency
write
(RAM only)

HED

•When Pr. 37 = "0" (factory setting)

H0000 to H2EE0 (0 to 120.00Hz): Set frequency in
0.01Hz increments
When changing the set frequency continuously, write it
to the inverter RAM (instruction code: HED).
The minimum setting increments are 0.01Hz but setting
can be made in only 0.1Hz increments.

•When Pr. 37 = "0.1 to 999", expansion link parameter

HFF = 0
H0000 to H03E7 (0 to 999): Set speed in 1r/min
increments

4 digits

(6 digits)

Set frequency
write (RAM
and E

2

PROM)

HEE

•When Pr. 37 = "0.1 to 999", expansion link parameter

HFF = 1
H0000 to HF3E58 (0 to 999.000): Set speed in 0.001r/
min increments
Set the number of data digits as 6 digits.
The minimum setting increments are 0.001r/min but
setting can be made in only 0.01r/min increments.

6 Inverter reset

HFD

H9696: Resets the inverter.
As the inverter is reset on start of communication by the
computer, the inverter cannot send reply data back to the
computer.

4 digits

7

Alarm
definition
batch clear

HF4

H9696: Alarm history batch clear

4 digits

No.

Item

Instruction

Code

Description

Number

of Data

Digits