beautypg.com

2 explanation of main circuit terminals – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 13

background image

3

Standard connection diagram and terminal specifications

1

WI

RING

Single-phase 200V power input
Single-phase 100V power input

1.1.2

Explanation of main circuit terminals

(1) Main circuit

CAUTION

To prevent a malfunction due to noise, keep the signal cables more than 10cm away
from the power cables.

REMARKS

To ensure safety, connect the power input to the inverter via a magnetic contactor and earth leakage
circuit breaker or no-fuse breaker, and use the magnetic contactor to switch power on-off.

The output is three-phase 200V.

Terminal

Symbol

Terminal Name

Description

R/L1, S/L2,

T/L3 (*1)

AC power input

Connect to the commercial power supply.

U, V, W

Inverter output

Connect a three-phase squirrel-cage motor.

P/+, PR (*2)

Brake resistor

connection

Connect the optional brake resistor (MRS/MYS type, FR-
ABR) (The brake resistor can be connected to the FR-
S520E-0.4K to 3.7K only.)

P/+, N/

Brake unit

connection

Connect the brake unit (BU), power regeneration
common converter (FR-CV) or high power factor
converter (FR-HC). (The N/- terminal is not provided for
the FR-S520E-0.1K to 0.75K.)

P/+, P1

Power factor

improving DC

reactor

connection

Remove the jumper across terminals P - P1 and connect
the optional power factor improving DC reactor (FR-
BEL(-H)).
(The single-phase 100V power input model cannot be
connected.)

Earth (ground)

For earthing (grounding) the inverter chassis. Must be
earthed (grounded).

*1. When using single-phase power input, terminals are R/L1 and S/L2.
*2. The PR terminal is provided for the FR-S520E-0.4K to 3.7K.

NFB

IM

U

V

W

MC

Power
supply

Motor

Earth (Ground)

S/L

2

R/L

1

This manual is related to the following products: