beautypg.com

MITSUBISHI ELECTRIC FR-S520E User Manual

Page 79

background image

69

Explanation of functions (parameters)

2

F

UNCT

IO

NS

2.3.3

Base frequency, base frequency voltage

(Pr.3 ,

Pr.19 ,

Pr.47 )

*1. 1.9 times greater than the power supply voltage for the FR-S510WE-0.1K to 0.75K.
*2. Twice greater than the power supply voltage for the FR-S510WE-0.1K to 0.75K.

•In Pr. 3 and Pr. 47, set the base frequency (motor's rated frequency).

Use the RT signal to switch between these two different base frequencies.
(Turn on the RT signal to make Pr. 47 valid.) (*)
When running the standard motor, generally set the "base frequency" to the rated
frequency of the motor. When running the motor using commercial power supply-
inverter switch-over operation, set the base frequency to the same value as the
power supply frequency.
If only "50Hz" is given on the motor rating plate as the frequency, always set the
"base frequency" to "50Hz". If it remains at "60Hz", the voltage may become too low
and torque shortage occurs, resulting in an overload trip. Special care must be taken
when "1" is set in Pr. 14 "load pattern selection".

•Set the base voltage (e.g. rated voltage of motor) in Pr. 19.

Used to adjust the inverter
outputs (voltage, frequency) to
the motor rating.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

3

Base frequency

60Hz

0 to 120Hz



19

Base frequency
voltage

- - -

0 to 800V,

888, - - -

888: 95% of power supply voltage (*1)
- - -: Same as power supply voltage (*2)
Setting is enabled when Pr. 30 = "1".

47

Second V/F
(base frequency)

- - -

0 to 120Hz,

- - -

- - -: Function invalid
Setting is enabled when Pr. 30 = "1".

CAUTION

1. Set 60Hz in Pr. 3 "base frequency" when using a Mitsubishi constant-torque

motor.

2. When automatic torque boost is selected, Pr. 47 is invalid. When automatic

torque boost is selected, setting "- - -" or "888" in Pr. 19 uses the rated
output voltage.

REMARKS

* The RT signal serves as the second function selection signal and makes the other second

functions valid.

Related parameters

When rated motor frequency is "50Hz"

Pr. 14 "load pattern selection" (refer to page 77)

RT signal (second function "Pr. 47") setting

Pr. 60 to Pr. 63 (input terminal function selection)

(refer to page 102)

Motor setting

Pr. 71 "applied motor" (refer to page 73)

Automatic torque boost selection

Pr. 98 "automatic torque boost selection (motor capacity)"
(refer to page 125)

Pr.19

Out

put

v

o

lt

age

Output

frequency (Hz)

Pr.3
Pr.47

This manual is related to the following products: