10 operation selection function parameters – MITSUBISHI ELECTRIC FR-S520E User Manual
Page 115
105
Operation selection function parameters
2
F
UNCT
IO
NS
2.10 Operation selection function parameters
2.10.1 Retry function (Pr. 66
, Pr. 67
, Pr. 68
, Pr. 69
)
•Use Pr. 66 to select the protective functions (major faults) to be activated for retries.
*
Indicates the retry items selected. (OCT denotes any of OC1 to OC3 and OVT
any of OV1 to OV3.)
•Use Pr. 67 to set the number of retries at alarm occurrence.
* If the retry count is exceeded, "
" (retry count over) is displayed.
•Use Pr. 68 to set the waiting time from when an inverter alarm occurs until a restart in
the range 0.1 to 360s.
•Reading the Pr. 69 value provides the cumulative number of successful restart times
made by retry. The cumulative number of time is cleared when setting value "0" is
written.
When any protective function (major fault) is activated and the inverter stops its
output, the inverter itself resets automatically and performs retries. Whether
retry is performed or not, alarms reset for retry, number of retries made and
waiting time can be selected.
When you have selected automatic restart after instantaneous power failure
(with speed search), restart operation is performed at the retry operation time
which is the same of that of a power failure. (Refer to page 96 for automatic
restart function.)
Parameter
Name
Factory
Setting
Setting
Range
Remarks
66
Retry selection
0
0 to 3
Setting is enabled when
Pr. 30 = "1"
67
Number of retries at alarm
occurrence
0
0, 1 to 10,
101 to 110
68
Retry waiting time
1s
0.1 to 360s
69
Retry count display erase
0
0
Pr. 66
Setting
Protective Functions (Major Faults) for Retries
OCT OVT THM THT
BE
FIN
GF
OHT OLT
PE
PUE RET CPU OPT
0
1
2
3
Pr. 67 Setting
Number of Retries
Alarm Signal Output
0
Retry is not made.
1 to 10
1 to 10 times
Not output every time *
101 to 110
1 to 10 times
Output every time