beautypg.com

2 operation and speed command source (n8 , n9 ), Age 152) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 162

background image

152

Communication parameters

2.16.2 Operation and speed command source (n8

, n9

)

The parameter numbers within parentheses are those for use of the parameter unit
(FR-PU04).

In the computer operation mode, commands from the external terminals and computer
are as listed below.
(Refer to page 102 for Pr. 60 to Pr. 63 (input terminal function selection).)

Used to make valid the operation and speed commands from the computer or
external terminals.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

n8 (338)

Operation
command source

0

0, 1

Setting is enabled when Pr. 30 = "1"

n9 (339)

Speed
command source

0

0, 1

Operation

location

selection

n8 (Pr. 338) "operation
command source"

0:

Computer

0:

Computer

1:

External

1:

External

Remarks

n9 (Pr. 339) "speed
command source"

0:

Computer

1:

External

0:

Computer

1:

External

Fixed
function
(Terminal-
equivalent
function)

Forward rotation command
(STF)

Computer Computer

External

External

Computer link operation
frequency

Computer

Computer

2

External

External

4

External

External

Sel

e

ct

io

n f

u

nc

ti

on

Pr

.

6

0

to

Pr

. 6

3

s

e

tti

n

g

s

0

Low-speed operation
command (RL)

Computer

External

Computer

External Pr. 59 = "0"

1

Middle-speed operation
command (RM)

Computer

External

Computer

External Pr. 59 = "0"

2

High-speed operation
command (RH)

Computer

External

Computer

External Pr. 59 = "0"

3

Second function
selection (RT)

Computer Computer

External

External

4

Current input selection
(AU)

Combined

Combined

5

Start self-holding
selection (STOP)

External

External

6 Output stop (MRS)

Combined Combined External

External Pr. 79

≠ "7"

7

External thermal relay
input (OH)

External

External

External

External

8

15-speed selection
(REX)

Computer

External

Computer

External Pr. 59 = "0"

9

Jog operation selection
(JOG)

External

External

10 Reset (RES)

External

External

External

External

14

PID control valid
terminal (X14)

Computer

External

Computer

External

16

PU-external operation
switch-over (X16)

External

External

External

External

---

Reverse rotation
command (STR)

Computer Computer

External

External

This manual is related to the following products: