164

Errors (Alarms)

*2. Functions only when any of Pr. 60 to Pr. 63 (input terminal function selection)

is set to OH.

Operation Panel Indication

GF

FR-PU04

Earth (Ground)

Fault

Name

Start-time output side earth (ground) fault overcurrent protection

Description

This function stops the inverter output if an earth (ground) fault
overcurrent flows due to an earth (ground) fault which occurred on
the inverter's output (load) side. Made valid when Pr. 40 "start-time
earth (ground) fault detection selection" = "1".

Check point

Check for an earth (ground) fault in the motor and connection
cable.

Corrective action

Remedy the earth (ground) fault portion.

Operation Panel Indication

OHT

FR-PU04

OH Fault

Name

External thermal relay (*2)

Description

If the external thermal relay provided for motor overheat protection
or the internally mounted temperature relay in the motor switches
on (contacts open), the inverter output is stopped. If the relay
contacts are reset automatically, the inverter will not restart unless
it is reset.

Check point

• Check for motor overheating.
• Check that the value of 7 (OH signal) is set correctly in any of Pr.

60 to Pr. 63 (input terminal function selection).

Corrective action

Reduce the load and operating duty.

Operation Panel Indication

OLT

FR-PU04

Stll Prev STP

Name

Stall prevention (overload)

Description

The running frequency has fallen to 0 by stall prevention operation
activated. OL appears while stall prevention is being activated.

Check point

Check the motor for use under overload.

Corrective action

Reduce the load weight.

Operation Panel Indication

OPT

FR-PU04

Option Fault

Name

Communication error

Description

Stops the inverter output if a setting error or connection (connector)
fault occurs during use of RS-485 communication function.

Check point

Check that the connector is plugged securely.

Corrective action

Make connection securely.
Please contact your sales representative.

Operation Panel Indication

PE

FR-PU04

Corrupt Memory

Name

Parameter storage device alarm

Description

A fault occurred in parameters stored
(example: E

2

PROM fault).

Check point

Check for too many number of parameter write times.

Corrective action

Please contact your sales representative.