2 output frequency detection (pr. 42 , pr. 43 ) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 101

background image

91

Output terminal function parameters

2

F

UNCT

IO

NS

2.4.2

Output frequency detection (Pr. 42

, Pr. 43

)

Refer to the above chart and set the corresponding parameters.
•When Pr. 43 "output frequency detection for reverse rotation" ≠ "- - -", the Pr.42

setting applies to forward rotation and the Pr.43 setting applies to reverse rotation.

•Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used

for FU signal output.

,

Refer to

,

(page 71).

Refer to

(page 67).

Refer to

(page 69).

The output frequency
detection signal (FU) is
output when the output
frequency reaches or
exceeds the setting. This
function can be used for
electromagnetic brake
operation, open signal, etc.
You can also set the
detection of the frequency
used exclusively for reverse
rotation.
This function is effective for switching the timing of electromagnetic brake
operation between forward rotation (rise) and reverse rotation (fall) during
vertical lift operation, etc.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

42

Output frequency
detection

6Hz

0 to 120Hz



Setting is
enabled when
Pr. 30 = "1".

43

Output frequency
detection for reverse
rotation

- - -

0 to 120Hz,

- - -

- - -: Same as

Pr. 42 setting

CAUTION

Using Pr. 64 or Pr. 65 to change the terminal assignment may affect the other
functions. Make setting after confirming the function of each terminal.

Related parameters

Assignment of FU signal to terminal

Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C

terminal function selection" (refer to page 104)

Forward

rotation

Reverse

rotation

Time

Output

signal

FU

Ou

tp

ut

fr

e

q

ue

ncy (Hz

)

Pr.42

Pr.43

ON

ON

OFF

OFF

OFF