176
Specification list
(3) Single-phase 200V power supply
*1. The applied motor capacity indicated is the maximum capacity applicable when a
Mitsubishi 4-pole standard motor is used.
*2. The rated output capacity indicated assumes that the output voltage is 230V.
*3. The % value of the overload current rating indicates the ratio of the overload current to the
inverter's rated output current.
For repeated duty, allow time for the inverter to return to or below the temperatures under
100% load.
*4. The maximum output voltage does not exceed the power supply voltage. The maximum
output voltage may be set as desired below the power supply voltage. However, the PWM
pulse voltage value of the inverter output side voltage remains unchanged at about
that of the power supply.
*5. The power supply capacity changes with the values of the power supply side inverter
impedances (including those of the input reactor and cables).
Type FR-S520SE-
K
0.1
0.2
0.4
0.75
1.5
Applied motor capacity (kW) (*1)
0.1
0.2
0.4
0.75
1.5
Ou
tp
u
t
Rated capacity (kVA) (*2)
0.3
0.5
1.0
1.6
2.8
Rated current (A)
0.8
1.4
2.5
4.1
7.0
Overload current rating (*3)
150% 60s, 200% 0.5s (Inverse time characteristics)
Voltage (*4)
Three phase, 200V to 240V 50Hz/60Hz
Po
we
r s
u
p
p
ly Rated input AC voltage/frequency
Single-phase, 200V to 240V 50Hz/60Hz
Permissible AC voltage fluctuation
170 to 264V 50Hz/60Hz
Permissible frequency fluctuation
±5%
Power supply system capacity
(kVA) (*5)
0.5
0.9
1.5
2.5
4.4
Protective structure (JEM1030)
Enclosed type (IP20)
Cooling system
Self-cooling
Forced air
cooling
Approximate mass (kg)
0.5
0.6
0.8
1.0
1.5
2