2 common specifications, Common specifications – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 188

background image

178

Specification list

4.1.2

Common specifications

Co

n

tr

o

l s

p

e

c

if

ic

a

ti

o

n

s

Control system

Selectable between Soft-PWM control and high carrier
frequency PWM control, V/F control or automatic torque
boost control are selectable.

Output frequency range

0.5 to 120Hz (starting frequency variable between 0 and
60Hz)

Frequency setting resolution

5VDC input: 1/500 of max. set frequency, 10VDC,
4 to 20mADC input: 1/1000 of max. set frequency
Digital input: 0.1Hz (less than 100Hz), 1Hz (100Hz or higher)

Frequency accuracy

Analog input: Within ±1% of max. output frequency
(25

°C±10°C)

Digital input: Within ±0.5% of set output frequency (when set
by the setting dial)

Starting torque

150% (at 5Hz) during automatic torque boost control

Acceleration/deceleration
time setting

0, 0.1 to 999s (acceleration and deceleration can be set
individually), linear or S-pattern acceleration/deceleration
mode can be selected.

Braking torque
(*2)

Regeneration

0.1K, 0.2K ... 150%, 0.4K, 0.75K ... 100%, 1.5K ... 50%,
2.2K, 3.7K ... 20%

DC injection
brake

Operation frequency (0 to 120Hz), operation time (0 to 10s),
operation voltage (0 to 15%)

In

put

si

gn

al

s

Frequency
setting
signal

Analog input 0 to 5VDC, 0 to 10VDC, 4 to 20mA

Digital input

Entered from operation panel

Start signal STF, STR

Forward and reverse rotation, start signal
automatic self-holding input (3-wire input) can be
selected.

Use
Pr. 60 to
Pr. 63 for
selection

Alarm reset

Used to reset alarm output provided when
protective function is activated.

Multi-speed selection

Up to 15 speeds can be selected. (Each speed
can be set between 0 and 120Hz, running speed
can be changed during operation from the
operation panel.)

Second function selection

Used to select second functions (acceleration
time, deceleration time, torque boost, base
frequency, electronic thermal relay function).

Output stop

Instantaneous shut-off of inverter output
(frequency, voltage)

Current input selection

Used to select frequency setting signal 4 to 20
mA (terminal 4).

External thermal relay
input

Thermal relay contact input for use when the
inverter is stopped by the external thermal relay.

Jog signal

Jog operation mode selection

PID control valid

Selection for exercising PID control

PU operation /external
operation switchover

Used to switch between PU operation and
external operation from outside the inverter.