2.16.1 Communication settings (n1
to n7
, n11
)
Communication-related parameters
• The parameter numbers within parentheses are those for use of the parameter unit
(FR-PU04).
• Refer to page 184 for the instruction codes.
Communication specifications
Parameter
Name
Factory
Setting
Setting
Range
Remarks
Reflection
Timing
n1(331)
Communication station number
0
0 to 31
Setting is enabled
when Pr. 30 = "1"
After reset
n2(332)
Communication speed
192
48,96,192
After reset
n3(333)
Stop bit length
1
0,1,10,11
After reset
n4(334)
Parity check presence/ absence
2
0,1,2
After reset
n5(335)
Number of communication
retries
1
0 to 10,
- - -
Immediately
n6(336)
Communication check time
interval (*)
---
0, 0.1 to
999s, - - -
Immediately
n7(337)
Waiting time setting
---
0 to
150ms,
- - -
After reset
n11(341) CR/LF selection
1
0,1,2
After reset
POINTS
*
When making RS-485 communication, set any value other than 0 in the
communication parameter n6 "communication check time interval". RS-485
communication is disabled if the setting is "0s".
Item
Computer
Conforming standard
EIA-485 (RS-485)
Number of inverters
connected
1:N (max. 32 inverters)
Communication speed
Selected between 19200, 9600 and 4800bps
Control protocol
Asynchronous
Communication method
Half-duplex
C
o
mmu
n
ic
a
tio
n
sp
ec
if
ic
at
io
n
s
Character system
ASCII (7 bits/8 bits) selectable
Stop bit length
Selectable between 1 bit and 2 bits.
Terminator
CR/LF (presence/absence selectable)
Check
system
Parity check Selectable between presence (even/odd) and absence
Sum check
Presence
Waiting time setting
Selectable between presence and absence
REMARKS
•For computer link operation, set 65535 (HFFFF) as the value "- - -"and 65520 (HFFF0) as the
Pr. 19 value "888".
•Refer to page 46 for handling the RS-485 connector.
•For parameter instruction codes, refer to the appended parameter instruction code list (page
184).