5 current detection function parameters, Current detection function parameters – MITSUBISHI ELECTRIC FR-S520E User Manual
Page 102
92
Current detection function parameters
2.5 Current detection function parameters
2.5.1
Output current detection functions
(Pr. 48
, Pr. 49
)
Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used for
Y12 signal output.
If the output remains higher than the
Pr. 48 setting during inverter operation
for longer than the time set in Pr. 49,
the output current detection signal
(Y12) is output from the inverter's open
collector output or contact output
terminal.
Parameter
Name
Factory
Setting
Setting
Range
Remarks
48
Output current
detection level
150%
0 to 200%
Setting is enabled when
Pr. 30 = "1"
49
Output current
detection period
0s
0 to 10s
Parameter
Number
Description
48
Set the output current detection level.
100% is the rated inverter current.
49
Set the output current detection period. Set the time from when the output
current has risen above the Pr. 48 setting until the output current detection
signal (Y12) is output.
CAUTION
•Once turned ON, when the output current has risen above the preset
detection level, the output current detection signal is held for at least 100ms
(approximately).
•Using Pr. 64 or Pr. 65 (output terminal function selection) to change terminal
assignment may affect the other functions. Make setting after confirming the
function of each terminal.
♦Related parameters♦
•
Assignment of Y12 signal to terminal
⇒
Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page 104)
Out
put
c
u
rre
nt
Time
Output current
detection
signal (Y12)
100ms
Pr.48
Pr.49
OFF
OFF
ON