beautypg.com

5 current detection function parameters, Current detection function parameters – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 102

background image

92

Current detection function parameters

2.5 Current detection function parameters

2.5.1

Output current detection functions

(Pr. 48

, Pr. 49

)

Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used for
Y12 signal output.

If the output remains higher than the
Pr. 48 setting during inverter operation
for longer than the time set in Pr. 49,
the output current detection signal
(Y12) is output from the inverter's open
collector output or contact output
terminal.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

48

Output current
detection level

150%

0 to 200%

Setting is enabled when
Pr. 30 = "1"

49

Output current
detection period

0s

0 to 10s

Parameter

Number

Description

48

Set the output current detection level.
100% is the rated inverter current.

49

Set the output current detection period. Set the time from when the output
current has risen above the Pr. 48 setting until the output current detection
signal (Y12) is output.

CAUTION

Once turned ON, when the output current has risen above the preset

detection level, the output current detection signal is held for at least 100ms
(approximately).

Using Pr. 64 or Pr. 65 (output terminal function selection) to change terminal

assignment may affect the other functions. Make setting after confirming the
function of each terminal.

Related parameters

Assignment of Y12 signal to terminal

Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C

terminal function selection" (refer to page 104)

Out

put

c

u

rre

nt

Time

Output current
detection
signal (Y12)

100ms

Pr.48

Pr.49

OFF

OFF

ON

This manual is related to the following products: