Input terminals

Start/Stop Timing Chart (for two-wire type)

Forward-Reverse Rotation Switch-Over Timing Chart

REMARKS

*1. The "starting frequency" in Pr. 13 (factory-set to 0.5Hz) may be set between 0 and 60Hz.
*2. If the next start signal is given during DC injection brake operation, the DC injection brake

is disabled and restart is made.

*3. The "DC injection brake operation time" in Pr. 11 (factory-set to 0.5s) may be set between

0 and 10s.

*4. The frequency at which the motor is coasted to a stop is not more than the "DC injection

brake operation frequency" set in Pr. 10 (factory setting = 3Hz; may be set between 0 and
120Hz) or not more than 0.5Hz.

*5. The "starting frequency" in Pr. 13, "DC injection brake operation time" in Pr. 11 and "DC

injection brake operation frequency" in Pr. 10 are the factory-set values.

DC injection
brake operation
time Pr. 11

O

u

tp

u

t f

reque

n

c

y

Starting frequency
Pr.13
(*1)

0.5Hz

ON

DC injection brake
operation
frequency Pr. 10

3Hz

0.5s

DC injection
brake operation
time Pr. 11

0.5Hz

0.5s

ON

0.5Hz

ON

3Hz

Coasted to

a stop

Time

DC injection brake
not operated

DC injection brake disabled

DC injection brake enabled

Start signal
terminal

(*4)

(*3)

(*3)

(*2)

Across STF-SD
Across STR-SD

O

u

tput

freq

uency

Starting
frequency
Pr.13
(*1)

0.5Hz

Forward
rotation

Forward

rotation

3Hz

3Hz

Start signal switched on
while DC injection brake
is being operated

DC injection brake operation
frequency Pr. 10

DC injection
brake enabled

Time

DC injection brake
operation time Pr. 11

0.5s

ON

ON

ON

ON

Reverse

rotation

0.5Hz

Start
signal
terminal

(*3)

(*4)

Across
STF-SD

Across
STR-SD