beautypg.com

MITSUBISHI ELECTRIC FR-S520E User Manual

Page 160

background image

150

Communication parameters

The corresponding error code in the following list is displayed if an error is detected in
any communication request data from the computer:

(5) Operation at alarm occurrence

*3: Can be selected using the corresponding parameter (factory-set to stop).

(6) Communication error

Error
Code

Item

Definition

Inverter

Operation

H0

Computer
NAK error

The number of errors consecutively detected in
communication request data from the computer is
greater than allowed number of retries.

Brought to an
alarm stop (OPT)
if error occurs
continuously
more than the
allowable number
of retries.

H1

Parity error The parity check result does not match the specified parity

H2

Sum check
error

The sum check code in the computer does not match
that of the data received by the inverter.

H3

Protocol
error

Data received by the inverter is in wrong protocol, data
receive is not completed within given time, or CR and
LF are not as set in the parameter.

H4

Framing
error

The stop bit length is not as specified by initialization.

H5

Overrun
error

New data has been sent by the computer before the
inverter completes receiving the preceding data.

H6







H7

Character
error

The character received is invalid (other than 0 to 9, A to
F, control code).

Does not accept
received data but
is not brought to
alarm stop

H8







H9







HA

Mode error

Parameter write was attempted in other than the computer
link operation mode or during inverter operation.

Does not accept
received data but
is not brought to
alarm stop.

HB

Instruction
code error

The specified command does not exist.

HC

Data range
error

Invalid data has been specified for parameter write,
frequency setting, etc.

HD







HE







HF







Fault Location

Status

Operation Mode

Communication

Operation

(RS-485 connector)

External Operation

Inverter fault

Inverter operation

Stop

Stop

Communication

RS-485
connector

Continued

Continued

Communication error
(Communication from
RS-485 connector)

Inverter operation

Stop/continued (*3)

Continued

Communication

RS-485
connector

Stop

Stop

Fault Location

Error Message

(Operation panel)

Remarks

Communication error
(Communication from RS-485 connector)

OPT

Error code is OPT