beautypg.com

MITSUBISHI ELECTRIC FR-S520E User Manual

Page 176

background image

166

Errors (Alarms)

(3) Warnings

*3. The stall prevention operation current can be set as desired. It is factory-set to

150%.

Operation Panel Indication

OL

FR-PU04

OL

Name

Stall prevention (overcurrent)

Description

During
acceleration

If a current of more than 150% (* 3) of the rated
inverter current flows in the motor, this function
stops the increase in frequency until the overload
current reduces to prevent the inverter from
resulting in overcurrent shut-off. When the overload
current has reduced below 150%, this function
increases the frequency again.

During
constant-
speed
operation

If a current of more than 150% (* 3) of the rated
inverter current flows in the motor, this function
lowers the frequency until the overload current
reduces to prevent overcurrent shut-off. When the
overload current has reduced below 150%, this
function increases the frequency up to the set
value.

During
deceleration

If a current of more than 150% (* 3) of the rated
inverter current flows in the motor, this function
stops the decrease in frequency until the overload
current reduces to prevent the inverter from
resulting in overcurrent shut-off. When the overload
current has reduced below 150%, this function
decreases the frequency again.

Check point

Check the motor for use under overload.

Corrective action

• The acceleration/deceleration time may change.
• Increase the stall prevention operation level with Pr. 22 "stall

prevention operation level", or disable stall prevention with Pr. 21
"stall prevention function selection".

• Check that the torque boost (Pr. 0) setting is not higher than

required.

Operation Panel Indication

oL

FR-PU04

oL

Name

Stall prevention (overvoltage)

Description

During
deceleration

If the regenerative energy of the motor increases
too much to exceed the brake capability, this
function stops the decrease in frequency to prevent
overvoltage shut-off. As soon as the regenerative
energy has reduced, deceleration resumes.

Check point

Check for sudden speed reduction.

Corrective action

The deceleration time may change. Increase the deceleration time
using Pr. 8 "deceleration time".

This manual is related to the following products: