Operation display – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 142

background image

132

Calibration parameters

Changing example

Deflecting the meter (analog indicator) to full-scale (1mA) at the
preset frequency of 60Hz (for frequency setting, refer to the
instruction manual (basic).)

POINT

•The calibration parameters "C1" can be made to be ready by setting "1" (extended

function parameter valid) in Pr. 30 "extended function display selection".

•Set the value of the calibration parameter C1 "FM terminal calibration".

(For details, refer to the instruction
manual (basic).)

MODE

4.

5.

Press the to enable setting.

SET

SET

3.

SET

8.

SET

Flicker ... Parameter setting complete!!

SET

6.

RUN

PU

EXT

RUN

RUN

+

-

7.

1.

MODE

Pr. 30 must be set to "1".

2.

Turn the to show

" "

.

Press the to show

SET

" "

.

The parameter
number read
previously
appears.

By turning the , you can read another parameter.

SET

Press the to return to the indication (step 3).

SET

Press the twice to show the next parameter ( ).

Press the to choose the
parameter setting mode.

Turn the until the
calibration parameter C1 "
terminal calibration" appears.

If the inverter is at a stop, press the

Press the .
Setting is complete.

Turn the to adjust the
indicator needle to the
desired position.

Analog indicator

to start it. (The motor

need not be connected.)

Operation

Display

In PU operation mode

FM