163

Errors (Alarms)

3

PROT

ECT

IVE F

UNCT

IONS

*1. Resetting the inverter initializes the internal thermal integratied data of the

electronic thermal relay function.

Operation Panel Indication

THM

FR-PU04

Motor Overload

Name

Motor overload shut-off (electronic thermal relay function) (* 1)

Description

The electronic thermal relay function in the inverter detects motor
overheat due to overload or reduced cooling capability during low-
speed operation to stop the inverter output. When a multi-pole
motor or two or more motors are run, provide a thermal relay on
the output side of the inverter.
Protection from burning due to motor temperature rise.

Check point

Check the motor for use under overload.

Corrective action

• Reduce the load weight.
• For a constant-torque motor, set the constant-torque motor in Pr.

71 "applied motor".

Operation Panel Indication

THT

FR-PU04

Inv. Overload

Name

Inverter overload shut-off (electronic thermal relay function) (* 1)

Description

If a current of more than 150% of the rated output current flows
and overcurrent shut-off does not occur (150% or less), inverse-
time characteristics cause the electronic thermal relay function to
be activated to stop the inverter output in order to protect the
output transistors.
Output transistor protection from overheat

Check point

Check the motor for use under overload.

Corrective action

Reduce the load weight.

Operation Panel Indication

FIN

FR-PU04

H/Sink O/Temp

Name

Fin overheat

Description

If the heatsink overheats, the temperature sensor is actuated to
stop the inverter output.

Check point

• Check for too high ambient temperature.
• Check for heatsink clogging.

Corrective action

Set the ambient temperature to within the specifications.

Operation Panel Indication

BE

FR-PU04

Br. Cct. Fault

Name

Brake transistor alarm detection (Available for the FR-S520E-0.4K
to 3.7K only.)

Description

This function stops the inverter output if an alarm occurs in the
brake circuit, e.g. damaged brake transistors.
In this case, the inverter must be powered off immediately.

Check point

• Reduce the load inertia.
• Check that the frequency of using the brake is proper.
• Check that the brake resistor selected is correct.

Corrective action

Replace the inverter.