Errors (Alarms)

(4) Write errors

Operation Panel Indication

Er1

FR-PU04

Control Mode

Name

Write disable error

Description

• Write was performed with "1" (write disable) set in Pr. 77

"parameter write disable selection".

• Frequency jump setting range overlapped.
• Parameter write was performed though the operation panel does

not have the write precedence.

Corrective action

• Check the setting of Pr. 77 "parameter write disable selection".

(Refer to page 112.)

• Check the settings of Pr. 31 to 36 (frequency jump). (Refer to

page 84.)

• When the FR-PU04 is fitted and n17 = "0" or "1", the operation of

the operation panel is invalid.
For RS-485 connector (RS-485) communication, the operation of
the operation panel is invalid.

Operation Panel Indication

Er2

FR-PU04

In PU/EXT Mode

OPERATOR ERR

Name

Write-while-running error/mode designation error

Description

• Write was performed during operation.
• An attempt was made to change the Pr. 79 setting to the

operation mode where the operation command has been input.

• Write was performed in the external operation mode.

Corrective action

• After stopping operation, make parameter setting.
• After setting the operation mode to the "PU operation mode",

make parameter setting. (Refer to page 113.)

Operation Panel Indication

Er3

FR-PU04

Incr I/P

Name

Calibration error

Description

Analog input bias and gain calibration values are too close.

Corrective action

Check the settings of C3, C4, C6 and C7 (calibration functions).
(Refer to page 86.)