10

Main circuit terminals

1.2.4

Selection of peripheral devices

Check the capacity of the motor applicable to the inverter you purchased. Appropriate
peripheral devices must be selected according to the capacity.
Refer to the following list and prepare appropriate peripheral devices:

1) Three-phase 200V power input

2) Three-phase 400V power input

Motor

Output

(kW)

Applied Inverter

Type

No-fuse Breaker

(NFB *1, 4) or

Earth Leakage

Circuit Breaker

(ELB) (Refer to
page 12
) (*2, 4)

Magnetic

Contactor

(MC)

(Refer to

page 16 )

Power Factor

Improving AC

Reactor

(Refer to page

17)

Power Factor

Improving DC

Reactor

(Refer to page

17)

0.1

FR-S520E-0.1K(-C)

30AF/5A

S-N10

FR-BAL-0.4K

(*3)

FR-BEL-0.4K

(*3)

0.2

FR-S520E-0.2K(-C)

30AF/5A

S-N10

FR-BAL-0.4K

(*3)

FR-BEL-0.4K

(*3)

0.4

FR-S520E-0.4K(-C)

30AF/5A

S-N10

FR-BAL-0.4K

FR-BEL-0.4K

0.75

FR-S520E-0.75K(-C)

30AF/10A

S-N10

FR-BAL-0.75K FR-BEL-0.75K

1.5

FR-S520E-1.5K(-C)

30AF/15A

S-N10

FR-BAL-1.5K

FR-BEL-1.5K

2.2

FR-S520E-2.2K(-C)

30AF/20A

S-N10

FR-BAL-2.2K

FR-BEL-2.2K

3.7

FR-S520E-3.7K(-C)

30AF/30A

S-N20,

S-N21

FR-BAL-3.7K

FR-BEL-3.7K

Motor

Output

(kW)

Applied Inverter

Type

No-fuse Breaker

(NFB *1, 4) or

Earth Leakage

Circuit Breaker

(ELB) (Refer to
page 12
) (*2, 4)

Magnetic

Contactor

(MC)

(Refer to

page 16)

Power Factor

Improving AC

Reactor

(Refer to page

17)

Power Factor

Improving DC

Reactor

(Refer to page

17)

0.4

FR-S540E-0.4K

30AF/5A

S-N10

FR-BAL-

H0.4K

FR-BEL-

H0.4K

0.75

FR-S540E-0.75K

30AF/5A

S-N10

FR-BAL-

H0.75K

FR-BEL-

H0.75K

1.5

FR-S540E-1.5K

30AF/10A

S-N10

FR-BAL-

H1.5K

FR-BEL-

H1.5K

2.2

FR-S540E-2.2K

30AF/15A

S-N10

FR-BAL-

H2.2K

FR-BEL-

H2.2K

3.7

FR-S540E-3.7K

30AF/20A

S-N20,

S-N21

FR-BAL-

H3.7K

FR-BEL-

H3.7K

This manual is related to the following products: